UPSMON.CONF(5)			  NUT Manual			UPSMON.CONF(5)

NAME
       upsmon.conf - Configuration for Network UPS Tools upsmon

DESCRIPTION
       This file’s primary job is to define the systems that upsmon(8) will
       monitor and to tell it how to shut down the system when necessary. It
       will contain passwords, so keep it secure. Ideally, only the upsmon
       process should be able to read it.

       Additionally, other optional configuration values can be set in this
       file.

CONFIGURATION DIRECTIVES
       DEADTIME seconds
	   upsmon allows a UPS to go missing for this many seconds before
	   declaring it "dead". The default is 15 seconds.

	   upsmon requires a UPS to provide status information every few
	   seconds (see POLLFREQ and POLLFREQALERT) to keep things updated. If
	   the status fetch fails, the UPS is marked stale. If it stays stale
	   for more than DEADTIME seconds, the UPS is marked dead.

	   A dead UPS that was last known to be on battery is assumed to have
	   changed to a low battery condition. This may force a shutdown if it
	   is providing a critical amount of power to your system. This seems
	   disruptive, but the alternative is barreling ahead into oblivion
	   and crashing when you run out of power.

	   Note: DEADTIME should be a multiple of POLLFREQ and POLLFREQALERT.
	   Otherwise, you’ll have "dead" UPSes simply because upsmon isn’t
	   polling them quickly enough. Rule of thumb: take the larger of the
	   two POLLFREQ values, and multiply by 3.

       FINALDELAY seconds
	   When running in master mode, upsmon waits this long after sending
	   the NOTIFY_SHUTDOWN to warn the users. After the timer elapses, it
	   then runs your SHUTDOWNCMD. By default this is set to 5 seconds.

	   If you need to let your users do something in between those events,
	   increase this number. Remember, at this point your UPS battery is
	   almost depleted, so don’t make this too big.

	   Alternatively, you can set this very low so you don’t wait around
	   when it’s time to shut down. Some UPSes don’t give much warning for
	   low battery and will require a value of 0 here for a safe shutdown.

	       Note
	       If FINALDELAY on the slave is greater than HOSTSYNC on the
	       master, the master will give up waiting for the slave to
	       disconnect.

       HOSTSYNC seconds
	   upsmon will wait up to this many seconds in master mode for the
	   slaves to disconnect during a shutdown situation. By default, this
	   is 15 seconds.

	   When a UPS goes critical (on battery + low battery, or "FSD":
	   forced shutdown), the slaves are supposed to disconnect and shut
	   down right away. The HOSTSYNC timer keeps the master upsmon from
	   sitting there forever if one of the slaves gets stuck.

	   This value is also used to keep slave systems from getting stuck if
	   the master fails to respond in time. After a UPS becomes critical,
	   the slave will wait up to HOSTSYNC seconds for the master to set
	   the FSD flag. If that timer expires, the slave will assume that the
	   master is broken and will shut down anyway.

	   This keeps the slaves from shutting down during a short-lived
	   status change to "OB LB" that the slaves see but the master misses.

       MINSUPPLIES num
	   Set the number of power supplies that must be receiving power to
	   keep this system running. Normal computers have just one power
	   supply, so the default value of 1 is acceptable.

	   Large/expensive server type systems usually have more, and can run
	   with a few missing. The HP NetServer LH4 can run with 2 out of 4,
	   for example, so you’d set it to 2. The idea is to keep the box
	   running as long as possible, right?

	   Obviously you have to put the redundant supplies on different UPS
	   circuits for this to make sense! See big-servers.txt in the docs
	   subdirectory for more information and ideas on how to use this
	   feature.

	   Also see the section on "power values" in upsmon(8).

       MONITOR system powervalue username password type
	   Each UPS that you need to be monitor should have a MONITOR line.
	   Not all of these need supply power to the system that is running
	   upsmon. You may monitor other systems if you want to be able to
	   send notifications about status changes on them.

       You must have at least one MONITOR directive in upsmon.conf.

       system is a UPS identifier. It is in this form:

       <upsname>[@<hostname>[:<port>]]

       The default hostname is "localhost". Some examples:

       ·   "su700@mybox" means a UPS called "su700" on a system called
	   "mybox". This is the normal form.

       ·   "fenton@bigbox:5678" is a UPS called "fenton" on a system called
	   "bigbox" which runs upsd(8) on port "5678".

       powervalue is an integer representing the number of power supplies that
       the UPS feeds on this system. Most normal computers have one power
       supply, and the UPS feeds it, so this value will be 1. You need a very
       large or special system to have anything higher here.

       You can set the powervalue to 0 if you want to monitor a UPS that
       doesn’t actually supply power to this system. This is useful when you
       want to have upsmon do notifications about status changes on a UPS
       without shutting down when it goes critical.

       The username and password on this line must match an entry in that
       system’s upsd.users(5). If your username is "monmaster" and your
       password is "blah", the MONITOR line might look like this:

       MONITOR myups@bigserver 1 monmaster blah master

       Meanwhile, the upsd.users on bigserver would look like this:

	   [monmaster]
		   password  = blah
		   upsmon master #  (or slave)

       The type refers to the relationship with upsd(8). It can be either
       "master" or "slave". See upsmon(8) for more information on the meaning
       of these modes. The mode you pick here also goes in the upsd.users
       file, as seen in the example above.

       NOCOMMWARNTIME seconds
	   upsmon will trigger a NOTIFY_NOCOMM after this many seconds if it
	   can’t reach any of the UPS entries in this configuration file. It
	   keeps warning you until the situation is fixed. By default this is
	   300 seconds.

       NOTIFYCMD command
	   upsmon calls this to send messages when things happen.

	   This command is called with the full text of the message as one
	   argument. The environment string NOTIFYTYPE will contain the type
	   string of whatever caused this event to happen.

	   If you need to use upssched(8), then you must make it your
	   NOTIFYCMD by listing it here.

	   Note that this is only called for NOTIFY events that have EXEC set
	   with NOTIFYFLAG. See NOTIFYFLAG below for more details.

	   Making this some sort of shell script might not be a bad idea. For
	   more information and ideas, see pager.txt in the docs directory.

	   Remember, this command also needs to be one element in the
	   configuration file, so if your command has spaces, then wrap it in
	   quotes.

	   NOTIFYCMD "/path/to/script --foo --bar"

	   This script is run in the background—that is, upsmon forks before
	   it calls out to start it. This means that your NOTIFYCMD may have
	   multiple instances running simultaneously if a lot of stuff happens
	   all at once. Keep this in mind when designing complicated
	   notifiers.

       NOTIFYMSG type message
	   upsmon comes with a set of stock messages for various events. You
	   can change them if you like.

	       NOTIFYMSG ONLINE "UPS %s is getting line power"

	       NOTIFYMSG ONBATT "Someone pulled the plug on %s"

	   Note that %s is replaced with the identifier of the UPS in
	   question.

	   The message must be one element in the configuration file, so if it
	   contains spaces, you must wrap it in quotes.

	       NOTIFYMSG NOCOMM "Someone stole UPS %s"

	   Possible values for type:

	   ONLINE
	       UPS is back online

	   ONBATT
	       UPS is on battery

	   LOWBATT
	       UPS is on battery and has a low battery (is critical)

	   FSD
	       UPS is being shutdown by the master (FSD = "Forced Shutdown")

	   COMMOK
	       Communications established with the UPS

	   COMMBAD
	       Communications lost to the UPS

	   SHUTDOWN
	       The system is being shutdown

	   REPLBATT
	       The UPS battery is bad and needs to be replaced

	   NOCOMM
	       A UPS is unavailable (can’t be contacted for monitoring)

       NOTIFYFLAG type flag[+flag][+flag]...
	   By default, upsmon sends walls global messages to all logged in
	   users) via /bin/wall and writes to the syslog when things happen.
	   You can change this.

	   Examples:

	       NOTIFYFLAG ONLINE SYSLOG
	       NOTIFYFLAG ONBATT SYSLOG+WALL+EXEC

	   Possible values for the flags:

	   SYSLOG
	       Write the message to the syslog

	   WALL
	       Write the message to all users with /bin/wall

	   EXEC
	       Execute NOTIFYCMD (see above) with the message

	   IGNORE
	       Don’t do anything

	       If you use IGNORE, don’t use any other flags on the same line.

       POLLFREQ seconds
	   Normally upsmon polls the upsd(8) server every 5 seconds. If this
	   is flooding your network with activity, you can make it higher. You
	   can also make it lower to get faster updates in some cases.

	   There are some catches. First, if you set the POLLFREQ too high,
	   you may miss short-lived power events entirely. You also risk
	   triggering the DEADTIME (see above) if you use a very large number.

	   Second, there is a point of diminishing returns if you set it too
	   low. While upsd normally has all of the data available to it
	   instantly, most drivers only refresh the UPS status once every 2
	   seconds. Polling any more than that usually doesn’t get you the
	   information any faster.

       POLLFREQALERT seconds
	   This is the interval that upsmon waits between polls if any of its
	   UPSes are on battery. You can use this along with POLLFREQ above to
	   slow down polls during normal behavior, but get quicker updates
	   when something bad happens.

	   This should always be equal to or lower than the POLLFREQ value. By
	   default it is also set 5 seconds.

	   The warnings from the POLLFREQ entry about too-high and too-low
	   values also apply here.

       POWERDOWNFLAG filename
	   upsmon creates this file when running in master mode when the UPS
	   needs to be powered off. You should check for this file in your
	   shutdown scripts and call upsdrvctl shutdown if it exists.

	   This is done to forcibly reset the slaves, so they don’t get stuck
	   at the "halted" stage even if the power returns during the shutdown
	   process. This usually does not work well on contact-closure UPSes
	   that use the genericups driver.

	   See the shutdown.txt file in the docs subdirectory for more
	   information.

       RBWARNTIME seconds
	   When a UPS says that it needs to have its battery replaced, upsmon
	   will generate a NOTIFY_REPLBATT event. By default, this happens
	   every 43200 seconds (12 hours).

	   If you need another value, set it here.

       RUN_AS_USER username
	   upsmon normally runs the bulk of the monitoring duties under
	   another user ID after dropping root privileges. On most systems
	   this means it runs as "nobody", since that’s the default from
	   compile-time.

	   The catch is that "nobody" can’t read your upsmon.conf, since by
	   default it is installed so that only root can open it. This means
	   you won’t be able to reload the configuration file, since it will
	   be unavailable.

	   The solution is to create a new user just for upsmon, then make it
	   run as that user. I suggest "nutmon", but you can use anything that
	   isn’t already taken on your system. Just create a regular user with
	   no special privileges and an impossible password.

	   Then, tell upsmon to run as that user, and make upsmon.conf
	   readable by it. Your reloads will work, and your config file will
	   stay secure.

	   This file should not be writable by the upsmon user, as it would be
	   possible to exploit a hole, change the SHUTDOWNCMD to something
	   malicious, then wait for upsmon to be restarted.

       SHUTDOWNCMD command
	   upsmon runs this command when the system needs to be brought down.
	   If it is a slave, it will do that immediately whenever the current
	   overall power value drops below the MINSUPPLIES value above.

	   When upsmon is a master, it will allow any slaves to log out before
	   starting the local shutdown procedure.

	   Note that the command needs to be one element in the config file.
	   If your shutdown command includes spaces, then put it in quotes to
	   keep it together, i.e.:

	       SHUTDOWNCMD "/sbin/shutdown -h +0"

SEE ALSO
       upsmon(8), upsd(8), nutupsdrv(8).

   Internet resources:
       The NUT (Network UPS Tools) home page: http://www.networkupstools.org/

Network UPS Tools		  08/07/2012			UPSMON.CONF(5)
[top]

List of man pages available for Mageia

Copyright (c) for man pages and the logo by the respective OS vendor.

For those who want to learn more, the polarhome community provides shell access and support.

[legal] [privacy] [GNU] [policy] [cookies] [netiquette] [sponsors] [FAQ]
Tweet
Polarhome, production since 1999.
Member of Polarhome portal.
Based on Fawad Halim's script.
....................................................................
Vote for polarhome
Free Shell Accounts :: the biggest list on the net