NUTUPSDRV(8)			  NUT Manual			  NUTUPSDRV(8)

NAME
       nutupsdrv - generic manual for unified NUT drivers

SYNOPSIS
       nutupsdrv -h

       nutupsdrv [OPTIONS]

DESCRIPTION
       nutupsdrv is not actually a driver. This is a combined man page for the
       shared code that is the core of many drivers within the Network UPS
       Tools package.

       For information on the specific drivers, see their individual man
       pages.

       UPS drivers provide a communication channel between the physical UPS
       hardware and the upsd(8) server. The driver is responsible for
       translating the native protocol of the UPS to the common format used by
       the rest of this package.

       The core has two modes of operation which are determined by the command
       line switches. In the normal mode, the driver will periodically poll
       the UPS for its state and parameters. The results of this command is
       presented to upsd. The driver will also handle setting variables and
       instant commands if available.

       The driver can also instruct the UPS to shut down the load, possibly
       after some delay. This mode of operation is intended for cases when it
       is known that the UPS is running out of battery power and the systems
       attached must be turned off to ensure a proper reboot when power
       returns.

	   Note
	   You probably don’t want to use any of these options directly. You
	   should use upsdrvctl(8) to control your drivers, and ups.conf(5) to
	   configure them. The rest of this manual describes options and
	   parameters that generally are not needed by normal users.

OPTIONS
       -h
	   Display a help message without doing anything else. This will also
	   list possible values for -x in that driver, and other help text
	   that the driver’s author may have provided.

       -a id
	   Autoconfigure this driver using the id section of ups.conf(5).
	   This argument is mandatory when calling the driver directly.

       -D
	   Raise the debugging level. Use this multiple times to see more
	   details. Running a driver in debug mode will prevent it from
	   backgrounding after startup. It will keep on logging information to
	   the console until it receives a SIGINT (usually Ctrl-C) or SIGTERM
	   signal.

	   The level of debugging needed depends both on the driver and the
	   problem you’re trying to diagnose. Therefore, first explain the
	   problem you have with a driver to a developer/maintainer, before
	   sending them debugging output. More often than not, if you just
	   pick a level, the output may be either too limited or too verbose
	   to be of any use.

       -q
	   Raise log level threshold. Use this multiple times to log more
	   details.

	   The debugging comment above also applies here.

       -i interval
	   Set the poll interval for the device.

       -V
	   Print only version information, then exit.

       -L
	   Print a parseable list of driver variables. Mostly useful for
	   configuration wizard programs.

       -k
	   ("Kill" power) Forced shutdown mode. The UPS will power off the
	   attached load, if possible.

	   You should use upsdrvctl shutdown whenever possible instead of
	   calling this directly.

       -r directory
	   The driver will chroot(2) to directory during initialization. This
	   can be useful when securing systems.

	   In addition to the state path, many systems will require /dev/null
	   to exist within directory for this to work. The serial ports are
	   opened before the chroot call, so you do not need to create them
	   inside the jail. In fact, it is somewhat safer if you do not.

       -u username
	   If started as root, the driver will setuid(2) to the user id
	   associated with username.

	   If you do not specify this value and start it as root, the driver
	   will switch to the default value that was compiled into the code.
	   This is typically nobody, and is far from ideal.

       -x var=val
	   Define a variable called var with the value of var in the driver.
	   This varies from driver to driver - see the specific man pages for
	   more information.

	   This is like setting var=val in ups.conf(5), but -x overrides any
	   settings from that file.

DIAGNOSTICS
       Information about the startup process is printed to stdout. Additional
       messages after that point are available in the syslog. After upsd(8)
       starts, the UPS clients such as upsc(8) can be used to query the status
       of an UPS.

PROGRAM CONTROL
       You should always use upsdrvctl(8) to control the drivers. While
       drivers can be started by hand for testing purposes, it is not
       recommended for production use.

FILES
       ups.conf
	   Required configuration file. This contains all details on which
	   drivers to start and where the hardware is attached.

BUGS
       Some of the drivers may have bugs. See their manuals for more
       information.

SEE ALSO
       Server: upsd(8)

       Clients: upsc(8), upscmd(8), upsrw(8), upslog(8), upsmon(8)

       CGI programs: upsset.cgi(8), upsstats.cgi(8), upsimage.cgi(8)

       Driver control: upsdrvctl(8)

       Drivers: apcsmart(8), bcmxcp(8), bcmxcp_usb(8), belkin(8),
       belkinunv(8), bestfcom(8), bestuferrups(8), bestups(8), blazer(8),
       cyberpower(8), dummy-ups(8), etapro(8), everups(8), gamatronic(8),
       genericups(8), isbmex(8), liebert(8), masterguard(8), metasys(8), mge-
       shut(8), mge-utalk(8), mge-xml(8), newmge-shut(8), nitram(8), oneac(8),
       optiups(8), powercom(8), powerman-pdu(8), powerpanel(8), rhino(8),
       richcomm_usb(8), safenet(8), snmp-ups(8), solis(8), tripplite(8),
       tripplitesu(8), tripplite_usb(8), usbhid-ups(8), upscode2(8),
       victronups(8)

       Internet resources: The NUT (Network UPS Tools) home page:
       http://www.networkupstools.org/

Network UPS Tools		  08/07/2012			  NUTUPSDRV(8)
[top]

List of man pages available for Mageia

Copyright (c) for man pages and the logo by the respective OS vendor.

For those who want to learn more, the polarhome community provides shell access and support.

[legal] [privacy] [GNU] [policy] [cookies] [netiquette] [sponsors] [FAQ]
Tweet
Polarhome, production since 1999.
Member of Polarhome portal.
Based on Fawad Halim's script.
....................................................................
Vote for polarhome
Free Shell Accounts :: the biggest list on the net