UPSCODE2(8)			  NUT Manual			   UPSCODE2(8)

NAME
       upscode2 - Driver for UPScode II compatible UPS equipment

NOTE
       This man page only documents the hardware-specific features of the
       upscode2 driver. For information about the core driver, see
       nutupsdrv(8).

SUPPORTED HARDWARE
       This driver supports UPS equipment which can be controlled via the
       UPScode II protocol. This is mainly Fiskars, Powerware equipment, but
       also some (probably OEM’ed) products from Compaq.

EXTRA ARGUMENTS
       This driver supports the following optional settings in the
       ups.conf(5):

       manufacturer=value
	   Autodetection of this parameter is not possible yet (and it
	   probably never will be). Therefore, this user-defined string
	   accepts any name. The default is unknown.

       input_timeout=value
	   The timeout waiting for a response from the UPS. Some UPS models
	   have shown to be rather slow, resulting in frequent messages about
	   empty responses from the UPS. If you see this, try increasing this
	   value.

       output_pace=value
	   Delay between characters sent to the UPS. This was added for
	   completeness with the above parameter. It has not shown to be
	   needed yet.

       baudrate=value
	   The default baudrate is 1200, which is the standard for the UPScode
	   II protocol.

       full_update_timer=value
	   Number of seconds between collection of normative values.

       use_crlf
	   Flag to set if commands towards to UPS need to be terminated with
	   CR-LF, and not just CR.

       use_pre_lf
	   Flag to set if commands towards to UPS need to be introduced with
	   an LF. A Compaq T1500h is known to need this.

COMMANDS
       The driver supports the following commands for those UPSen that support
       them. The available commands are autodetected during initialization, so
       you should check availability with upscmd -l.

       ·   test.panel.start - Start UPS self test

       ·   test.battery.start - Start battery self test

       ·   beeper.enable - Enable UPS beeper

       ·   beeper.disable - Disable UPS beeper

       ·   shutdown.return - Shut down in 1 second and wait for power to
	   return

       ·   shutdown.stayoff - Shut down in 1 seconds

       ·   shutdown.reboot - Shut down in 1 seconds and reboot after 1 minute

       ·   shutdown.reboot.graceful - Shut down in 20 seconds and reboot after
	   1 minute

NOTES
       The Powerware UPS models that this driver has been tested against until
       now have not returned a value for battery.charge. Therefore, the driver
       will guestimate a value based on the nominal battery min/max and the
       current battery voltage.

AUTHOR
       Håvard Lygre <hklygre@online.no>, Niels Baggesen <niels@baggesen.net>

SEE ALSO
   The core driver:
       nutupsdrv(8)

   Internet resources:
       The NUT (Network UPS Tools) home page: http://www.networkupstools.org/

Network UPS Tools		  08/07/2012			   UPSCODE2(8)
[top]

List of man pages available for Mageia

Copyright (c) for man pages and the logo by the respective OS vendor.

For those who want to learn more, the polarhome community provides shell access and support.

[legal] [privacy] [GNU] [policy] [cookies] [netiquette] [sponsors] [FAQ]
Tweet
Polarhome, production since 1999.
Member of Polarhome portal.
Based on Fawad Halim's script.
....................................................................
Vote for polarhome
Free Shell Accounts :: the biggest list on the net