SNMP-UPS(8)			  NUT Manual			   SNMP-UPS(8)

NAME
       snmp-ups - Multi-MIB Driver for SNMP UPS equipment

NOTE
       This man page only documents the hardware-specific features of the
       snmp-ups driver. For information about the core driver, see
       nutupsdrv(8).

SUPPORTED HARDWARE
       The snmp-ups driver automatically detects and supports a wide range of
       devices by loading various MIBS: ietf:: UPS that is RFC 1628 (UPS MIB)
       compliant, e.g. MGE UPS SYSTEMS, Liebert, perhaps others (default)

       mge
	   MGE UPS SYSTEMS and MGE Office Protection Systems devices with SNMP
	   cards (ref 66062, 66045, 66074 and 66244)

       apcc
	   APC AP9605, AP9606, AP9617, and AP9618 APC network management
	   cards, as well as any others supporting the APC POWERNET MIB

       netvision
	   Socomec Sicon UPS with Netvision Web/SNMP management card/external
	   box

       pw
	   Powerware devices with ConnectUPS SNMP cards

       aphel_genesisII
	   Eaton Powerware ePDU Monitored

       aphel_revelation
	   Eaton Powerware ePDU Managed

       raritan
	   Various Raritan PDUs

       baytech
	   Various BayTech PDUs

       cpqpower
	   HP/Compaq AF401A management card, perhaps others

       cyberpower
	   Cyberpower RMCARD201. Should also support RMCARD100 (net version),
	   RMCARD202 and RMCARD301

EXTRA ARGUMENTS
       This driver supports the following optional settings in the
       ups.conf(5):

       mibs=name
	   Set MIB compliance (default=auto, allowed entries: refer to the
	   above SUPPORTED HARDWARE). With "auto", the driver will try a
	   select set of SNMP objects until it finds one that the device
	   responds to.

       community=name
	   Set community name (default = public). Note that you require a RW
	   community name to change UPS settings (as for a powerdown).

       snmp_version=version
	   Set SNMP version (default = v1, the other allowed value is v2c)

       pollfreq=value
	   Set polling frequency in seconds, to reduce network flow
	   (default=30)

       notransferoids
	   Disable the monitoring of the low and high voltage transfer OIDs in
	   the hardware. This will remove input.transfer.low and
	   input.transfer.high from the list of variables. This should only be
	   used on APCC Symmetra equipment which has strangeness in the
	   three-phase power reporting.

       secLevel=value
	   Set the securityLevel used for SNMPv3 messages
	   (default=noAuthNoPriv, allowed: authNoPriv,authPriv)

       secName=value
	   Set the securityName used for authenticated SNMPv3 messages (no
	   default)

       authPassword=value
	   Set the authentication pass phrase used for authenticated SNMPv3
	   messages (no default)

       privPassword=value
	   Set the privacy pass phrase used for encrypted SNMPv3 messages (no
	   default)

       authProtocol=value
	   Set the authentication protocol (MD5 or SHA) used for authenticated
	   SNMPv3 messages (default=MD5)

       privProtocol=value
	   Set the privacy protocol (DES or AES) used for encrypted SNMPv3
	   messages (default=DES)

REQUIREMENTS
       You will need to install the Net-SNMP package from
       http://www.net-snmp.org/ before building this driver.

       SNMP v3 also requires OpenSSL support from http://www.openssl.org.

LIMITATION
   Shutdown
       This driver does not provide a proper upsdrv_shutdown() function. There
       probably never will be one, since at the time this script should run
       (near the end of the system halt script), there will be no network
       capabilities anymore. Probably the only way to shutdown an SNMP UPS is
       by sending it a shutdown with delay command through upscmd(8) and hope
       for the best that the system will have finished shutting down before
       the power is cut.

INSTALLATION
       This driver is only built if the Net-SNMP development files are present
       on the system. You can also force it to be built by using "configure
       --with-snmp=yes" before calling make.

IMPLEMENTATION
       The hostname of the UPS is specified with the "port" value in ups.conf,
       i.e.:

	   [snmpv1]
		   driver = snmp-ups
		   port = snmp-ups.example.com
		   community = public
		   snmp_version = v1
		   mibs = ietf
		   pollfreq = 15
		   desc = "Example SNMP v1 device"

	   [snmpv3]
		   driver = snmp-ups
		   port = 166.99.224.132
		   mibs = mge
		   secLevel = authPriv
		   secName = mysecurityname
		   authPassword = myauthenticationpassphrase
		   privPassword = myprivatepassphrase
		   desc = "Example SNMP v3 device, with the highest security level"

AUTHORS
       Arnaud Quette, Dmitry Frolov

       Sponsored by Eaton http://www.eaton.com and originally by MGE UPS
       SYSTEMS http://www.mgeups.com/

SEE ALSO
   The core driver:
       nutupsdrv(8)

   NUT SNMP Protocols Library
       Available at: http://www.networkupstools.org/protocols/snmp/

   Internet resources:
       The NUT (Network UPS Tools) home page: http://www.networkupstools.org/

Network UPS Tools		  08/07/2012			   SNMP-UPS(8)
[top]

List of man pages available for Mageia

Copyright (c) for man pages and the logo by the respective OS vendor.

For those who want to learn more, the polarhome community provides shell access and support.