ONEAC(8)			  NUT Manual			      ONEAC(8)

NAME
       oneac - Driver for Oneac UPS equipment

NOTE
       This man page only documents the hardware-specific features of the
       oneac driver. For information about the core driver, see nutupsdrv(8).

SUPPORTED HARDWARE
       This driver supports various Oneac UPS families:

       ·   EG (late 80s, early 90s, plug-in serial interface card)

       ·   ON (early and mid-90s, plug-in serial interface card)

       ·   OZ (mid-90s on, DB-25 std., interface slot)

       ·   OB (early 2000’s on, big cabinet, DB-25 std., interface slot)

       If your UPS is equipped with the Basic Interface card, use the
       genericups(8) driver.

EXTRA ARGUMENTS
       This driver supports the following optional settings in the ups.conf(5)
       file:

       testtime=num
	   Change battery test time from the 2 minute default.

       offdelay=num
	   Change shutdown delay time from 0 second default.

INSTANT COMMANDS
       This driver supports the following Instant Commands. (See upscmd(8))

   All UPS units
       shutdown.return
	   Turn off the load possibly after a delay and return when power is
	   back.

       shutdown.stop
	   Stop a shutdown in progress.

       shutdown.reboot
	   Shut down the load briefly while rebooting the UPS.

       test.failure.start
	   Starts a 15 second long simulation of an input power failure.

       test.battery.start.quick
	   Start a "quick" battery test. The default time is 2 minutes. This
	   time can be set in the ups.conf file. See testime above.

       test.battery.stop
	   Stops a battery test that is in progress.

   All ON UPS units
       reset.input.minmax
	   Reset the minimum and maximum input line voltage values seen since
	   the last reset or power on.

   Newer ON UPS units
       test.panel.start
	   Start testing the UPS panel.

       test.battery.start.deep
	   Start a "deep" battery test. This test runs the UPS until the low
	   battery point and then returns to the AC line.

       reset.input.minmax
	   Reset the minimum and maximum input line voltage values seen since
	   the last reset or power on.

       beeper.enable
	   Enable UPS beeper/buzzer.

       beeper.disable
	   Disable UPS beeper/buzzer.

       beeper.mute
	   Mutes the UPS beeper/buzzer for the current alarm condition(s).

WRITABLE VARIABLES
       See upsrw(8) to see what variables are writable for the UPS.

	   Note
	   If your UPS supports writing battery.runtime.low, the new set value
	   is to be entered in minutes (up to 99) but the reported value is
	   reported in seconds (set value * 60).

	   Note
	   If your UPS supports input.transfer.low and input.transfer.high,
	   those values are used to create an allowable output range. The UPS
	   will do what it can to keep the output voltage value within the
	   defined range (for example: tap change or switch to inverter).

AUTHOR
       Bill Elliot <bill@wreassoc.com>, Eric Lawson <elawson@inficad.com>

SEE ALSO
   The core driver:
       nutupsdrv(8)

   Internet resources:
       The NUT (Network UPS Tools) home page: http://www.networkupstools.org/

Network UPS Tools		  08/07/2012			      ONEAC(8)
[top]

List of man pages available for Mageia

Copyright (c) for man pages and the logo by the respective OS vendor.

For those who want to learn more, the polarhome community provides shell access and support.

[legal] [privacy] [GNU] [policy] [cookies] [netiquette] [sponsors] [FAQ]
Tweet
Polarhome, production since 1999.
Member of Polarhome portal.
Based on Fawad Halim's script.
....................................................................
Vote for polarhome
Free Shell Accounts :: the biggest list on the net