POWERCOM(8)		    Network UPS Tools (NUT)		   POWERCOM(8)

NAME
       powercom - UPS driver for Powercom/Trust/Advice UPS equipment

NOTE
       This man page only documents the hardware‐specific features of the pow‐
       ercom driver.  For information about the core driver, see nutupsdrv(8).

SUPPORTED HARDWARE
       This driver supports many similar kinds of UPS hardware.	 The most com‐
       mon  ones  are  the  Trust  425/625,  Powercom, and Advice Partner/King
       PR750.  Others using the same protocol may also work.

EXTRA ARGUMENTS
       This  driver  supports  the  following	optional   settings   in   the
       ups.conf(5):

       linevoltage=value
	      An  integer  specifying  the  mains  voltage.  It	 can't be auto
	      detected.	 Acceptable values are in  the	range  of  110‐120  or
	      220‐240. The default is 230.

       manufacturer=name
	      Specify	the  manufacturer  name,  which	 also  can't  be  auto
	      detected. This is a user defined string so any name  is  accept‐
	      able. The default is PowerCom.

       modelname=name
	      Specify  the model name, which also can't be auto detected. This
	      is a user defined string so any name is acceptable. The  default
	      is Unknown.

       serialnumber=value
	      Like  modelname above, but for the serial number. The default is
	      Unknown.

       type=name
	      The exact type of the communication protocol within the powercom
	      family,  that will be used to communicate with the UPS. The type
	      is named after the first modelname that was coded with that pro‐
	      tocol.  The acceptable names are KP625AP, Trust, Egys, KIN, BNT,
	      IMP and BNT-other. The default is Trust.	 BNT-other  -  it's  a
	      special  type  for  BNT 100-120V models for this type you can (I
	      think must!) specify voltage, batteryPercentage,	loadPercentage
	      and validationSequence.

       numOfBytesFromUPS=value
	      The  number  of bytes in a UPS frame. The default is type depen‐
	      dant and is given below.

       methodOfFlowControl=name
	      The method of serial communication flow control that is  engaged
	      by  the  UPS.  The default is type dependant and is given below.
	      Acceptable names are dtr0rts1, dtr1 or no_flow_control.

       shutdownArguments={{minutes,seconds},whether_minutes_should_be_used}
	      The minutes and seconds that the UPS should wait between receiv‐
	      ing  the	shutdown  command and actually shutting off. The other
	      argument should be set to the character n only when the  minutes
	      value  should be skipped and not sent to the UPS. The default is
	      type dependant and is given below. The  braces  and  commas  are
	      mandatory. Note that there should be no white space characters.

       voltage={coefficient1,coefficient2,coefficient3,coefficient4}
	      Only  for	 KP625AP,  Trust,  Egys, BNT-other A quad that is used
	      convert the raw data to  human  readable	voltage	 reading.  The
	      default  is  type dependant and is given below. Do note that the
	      braces and commas are mandatory, as well as the  lack  of	 white
	      space characters.

       frequency={coefficient1,coefficient2}
	      Only  for KP625AP, Trust, Egys A pair to convert the raw data to
	      human readable frequency reading. The default is type  dependant
	      and  is  given  below.  Do  note	that the braces and commas are
	      mandatory as well, as the lack of white space characters.

       batteryPercentage={coefficient1,coefficient2,coefficient3,coeffi‐
       cient4,coefficient5}
	      Only  for	 KP625AP,  Trust, Egys, BNT-other A 5 tuple to convert
	      the raw data to human readable battery percentage	 reading.  The
	      default  is  type dependant and is given below. Do note that the
	      braces and commas are mandatory, as  the	lack  of  white	 space
	      characters.

       loadPercentage={coefficient1,coefficient2,coefficient3,coefficient4}
	      Only  for	 KP625AP, Trust, Egys, BNT-other A quad to convert the
	      raw data to human readable load percentage reading. The  default
	      is  type	dependant  and is given below. Do note that the braces
	      and commas are mandatory, as the lack of white space characters.

       validationSequence={{index1,value1},{index2,value2},{index3,value3}}
	      Only for KP625AP, Trust, Egys, BNT-other 3 pairs to be used  for
	      validating  the UPS by comparing bytes of the raw data with con‐
	      stant values. The default is type dependant and is given	below.
	      The  braces and commas are mandatory, as the lack of white space
	      characters.

DEFAULT VALUES FOR THE EXTRA ARGUMENTS
       linevoltage = 230

       manufacturer = PowerCom

       modelname = Unknown

       serialnumber = Unknown

       type = Trust

       The rest of the default values for the extra arguments are type	depen‐
       dant:

       Trust

	      numOfBytesFromUPS = 11

	      methodOfFlowControl = dtr0rts1

	      validationSequence = {{5,0},{7,0},{8,0}}

	      shutdownArguments = {{0,10},n}

	      frequency = {0.00020997,0.00020928}

	      loadPercentage = {6.1343,-0.3808,4.3110,0.1811}

	      batteryPercentage = {5.0000,0.3268,-825.00,4.5639,-835.82}

	      voltage = {1.9216,-0.0977,0.9545,0.0000}

       KP625AP

	      numOfBytesFromUPS = 16

	      methodOfFlowControl = dtr0rts1

	      validationSequence = {{5,0x80},{7,0},{8,0}}

	      shutdownArguments = {{0,10},n}

	      frequency = {0.00020997,0.00020928}

	      loadPercentage = {6.1343,-0.3808,4.3110,0.1811}

	      batteryPercentage = {5.0000,0.3268,-825.00,4.5639,-835.82}

	      voltage = {1.9216,-0.0977,0.9545,0.0000}

       Egys

	      numOfBytesFromUPS = 16

	      methodOfFlowControl = no_flow_control

	      validationSequence = {{5,0x80},{7,0},{8,0}}

	      shutdownArguments = {{0,10},n}

	      frequency = {0.00020997,0.00020928}

	      loadPercentage = {6.1343,-0.3808,1.3333,0.6667}

	      batteryPercentage = {5.0000,0.3268,-825.00,2.2105,-355.37}

	      voltage = {1.9216,-0.0977,0.9545,0.0000}

       IMP

	      numOfBytesFromUPS = 16

	      methodOfFlowControl = no_flow_control

	      validationSequence = {{5,0xFF},{7,0},{8,0}}

	      shutdownArguments = {{1,30},y}

       KIN

	      numOfBytesFromUPS = 16

	      methodOfFlowControl = no_flow_control

	      validationSequence = {{11,0x4b},{8,0},{8,0}}

	      shutdownArguments = {{1,30},y}

       BNT

	      numOfBytesFromUPS = 16

	      methodOfFlowControl = no_flow_control

	      validationSequence = {{11,0x42},{8,0},{8,0}}

	      shutdownArguments = {{1,30},y}

       BNT-other

	      numOfBytesFromUPS = 16

	      methodOfFlowControl = no_flow_control

	      validationSequence = {{8,0},{8,0},{8,0}}

	      shutdownArguments = {{1,30},y}

	      loadPercentage = {1.4474,0.0,0.8594,0.0}

	      batteryPercentage = {5.0000,0.3268,-825.00,0.46511,0}

	      voltage = {1.9216,-0.0977,0.82857,0.0000}

AUTHOR
       Peter Bieringer <pb@bieringer.de> Alexey Sidorov <alexsid@altlinux.org>

SEE ALSO
   The core driver:
       nutupsdrv(8)

   Internet resources:
       The NUT (Network UPS Tools) home page: http://www.networkupstools.org/

				Fri Jan 25 2008			   POWERCOM(8)
[top]

List of man pages available for Mandriva

Copyright (c) for man pages and the logo by the respective OS vendor.

For those who want to learn more, the polarhome community provides shell access and support.

[legal] [privacy] [GNU] [policy] [cookies] [netiquette] [sponsors] [FAQ]
Tweet
Polarhome, production since 1999.
Member of Polarhome portal.
Based on Fawad Halim's script.
....................................................................
Vote for polarhome
Free Shell Accounts :: the biggest list on the net